{"product_id":"abb-fi830f-3bdh000032r1-fieldbus-module-freelance-ac-800f-series","title":"ABB FI830F 3BDH000032R1 Fieldbus Module Freelance AC 800F Series","description":"\u003cp\u003eThe FI830F 3BDH000032R1, also cataloged as the FI830F Fieldbus Modules, operates as a dedicated hardware component for signal processing or control execution within industrial automation architectures. The hardware serves as a communication interface between the controller base unit and field devices via the PROFIBUS DP protocol. It supports master functionality to coordinate up to 126 slave nodes, offloading cyclic data exchange tasks from the main central processing unit to optimize bus cycle times.\u003c\/p\u003e\n\u003ch3\u003eTechnical Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eFI830F 3BDH000032R1\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eABB\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOrigin\u003c\/td\u003e\n\u003ctd\u003eSweden\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e0.15 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions\u003c\/td\u003e\n\u003ctd\u003e2.7 x 12.6 x 15.4 cm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temperature\u003c\/td\u003e\n\u003ctd\u003e-20 to 60 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eStorage Temperature\u003c\/td\u003e\n\u003ctd\u003e-40 to 85 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Voltage\u003c\/td\u003e\n\u003ctd\u003e24 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRelative Humidity\u003c\/td\u003e\n\u003ctd\u003e5% to 95% non-condensing\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInterface Type\u003c\/td\u003e\n\u003ctd\u003ePROFIBUS DP\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePhysical Layer\u003c\/td\u003e\n\u003ctd\u003eRS-485\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTransmission Speed\u003c\/td\u003e\n\u003ctd\u003e9.6 kbps to 12 Mbps\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMaximum Number of Slaves\u003c\/td\u003e\n\u003ctd\u003e126 nodes\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOn-board Memory\u003c\/td\u003e\n\u003ctd\u003e256 KB shared memory\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eController Compatibility\u003c\/td\u003e\n\u003ctd\u003ePM 802F, PM 803F\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTariff Code\u003c\/td\u003e\n\u003ctd\u003e8537101190\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eBrand-Specific Technical Block\u003c\/h3\u003e\n\u003cp\u003eThe module interfaces directly with the ABB Freelance AC 800F backplane communication structure via specialized dual-port shared memory. The internal 256 KB memory buffer decouples the fieldbus cycle from the controller task execution interval, ensuring deterministic scanning profiles. It communicates with the host PM 802F or PM 803F processor nodes over the parallel system bus.\u003c\/p\u003e\n\u003cp\u003eFor line redundancy configurations, the physical RS-485 interface connects to external RLM01 redundancy modules to duplicate the transmission paths. The firmware architecture handles PROFIBUS DP V1 acyclic services for asset management parameters alongside standard cyclic I\/O mapping, maintaining complete protocol isolation between the field level and the processing core.\u003c\/p\u003e\n\u003ch3\u003eOrdering Information\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eStandard Package: ABB FI830F 3BDH000032R1 hardware module, factory anti-static packaging, product label sheet.\u003c\/li\u003e\n\u003cli\u003eOptional Accessories: RLM01 Redundancy Link Module, standard PROFIBUS DP bus connectors, standard DIN rail mount hardware.\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eInstallation Guidelines\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eMounting and Slot Insertion: The module inserts into any of the 4 available option slots on the PM 802F\/PM 803F base unit. Ensure the DIN rail meets standard specifications and the controller chassis connects to the central functional earth terminal.\u003c\/li\u003e\n\u003cli\u003eWiring and Shielding: Connect the PROFIBUS DP cable using shielded twisted-pair medium. The cable shield must expose electrical contact to the metallic connector shell for grounding via the module interface frame.\u003c\/li\u003e\n\u003cli\u003eTermination: Active termination resistors must operate at both physical ends of the PROFIBUS DP segment. Do not enable termination on intermediate nodes.\u003c\/li\u003e\n\u003cli\u003eThermal management: Maintain 50 mm clearance above and below the controller assembly to ensure passive convective airflow within the specified operating boundaries.\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eFrequently Asked Questions\u003c\/h3\u003e\n\u003cp\u003eQ: What is the behavior of the module during a hot-swap procedure?\u003c\/p\u003e\n\u003cp\u003eA: The module can be extracted or inserted while the controller is powered, triggering an automated driver initialization sequence without stopping the CPU.\u003c\/p\u003e\n\u003cp\u003eQ: How does the module handle backplane load current?\u003c\/p\u003e\n\u003cp\u003eA: It draws its primary logic operating current directly from the 24 VDC system backplane bus provided by the controller base unit.\u003c\/p\u003e\n\u003cp\u003eQ: What is the redundancy switching delay when paired with an RLM01 module?\u003c\/p\u003e\n\u003cp\u003eA: Switching occurs at the physical layer within the microsecond range, maintaining uninterrupted data flow to the active controller node.\u003c\/p\u003e\n\u003cp\u003eQ: Which firmware versions are compatible with the FI830F module?\u003c\/p\u003e\n\u003cp\u003eA: The module requires Freelance software version 6.2 or higher for proper diagnostic mapping and hardware description file recognition.\u003c\/p\u003e\n\u003cp\u003eQ: What level of electrical signal isolation does the PROFIBUS interface provide?\u003c\/p\u003e\n\u003cp\u003eA: The RS-485 interface features galvanic isolation up to 500 VAC between the field networks and the internal backplane logic circuit.\u003c\/p\u003e\n\u003cp\u003eQ: What are the field wiring constraints regarding maximum cable length at 12 Mbps?\u003c\/p\u003e\n\u003cp\u003eA: At the maximum transmission speed of 12 Mbps, the copper segment length must not exceed 100 meters without repeating hardware.\u003c\/p\u003e\n\u003cp\u003eQ: Can the module act as a PROFIBUS DP slave device?\u003c\/p\u003e\n\u003cp\u003eA: No, the hardware architecture is fixed to operate exclusively as a master station class 1 or class 2 on the network.\u003c\/p\u003e\n\u003cp\u003eQ: How is the PROFIBUS node address assigned to the module?\u003c\/p\u003e\n\u003cp\u003eA: The address configuration is defined within the Freelance engineering software tool and downloaded directly to the controller non-volatile memory.\u003c\/p\u003e","brand":"ABB","offers":[{"title":"Default Title","offer_id":46021145329837,"sku":"FI830F 3BDH000032R1","price":88.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0733\/1613\/9181\/files\/FI830F_14.jpg?v=1784167544","url":"https:\/\/www.maxwellplc.com\/ru\/products\/abb-fi830f-3bdh000032r1-fieldbus-module-freelance-ac-800f-series","provider":"Maxwell PLC Ltd","version":"1.0","type":"link"}