{"product_id":"nx-da3605-omron-analog-output-module-sysmac-nx-series","title":"NX-DA3605 Omron Analog Output Module Sysmac NX Series","description":"\u003cp\u003eThe \u003cstrong\u003eOmron NX-DA3605\u003c\/strong\u003e, also cataloged as the \u003cstrong\u003eNX-DA3605\u003c\/strong\u003e Analog Output Module, operates as a dedicated hardware component for high-speed linear voltage output generation within Sysmac NX Series automation platforms. Configured with 4 analog output channels, it converts digital controller values into -10 to +10 V analog signals at a 15-bit resolution. The module executes synchronous signal processing with a conversion time of 0.04 ms per unit across the NX I\/O bus, facilitating precise closed-loop motion and actuator control.\u003c\/p\u003e\n\u003ch3\u003eModel Numbering \u0026amp; Decoding Structure\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eNX\u003c\/strong\u003e: Sysmac modular slice I\/O series hardware platform designation.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eDA\u003c\/strong\u003e: Dedicated analog digital-to-analog output unit classification.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003e3\u003c\/strong\u003e: High-performance voltage output functional specification with 15-bit conversion resolution.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003e6\u003c\/strong\u003e: 4-channel analog output point capacity allocation.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003e05\u003c\/strong\u003e: Linear voltage output signal range configuration (-10 to +10 V).\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eTechnical Specifications Matrix\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eNX-DA3605\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eOmron\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOrigin\u003c\/td\u003e\n\u003ctd\u003eJapan\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e0.07 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eShipping Dimensions\u003c\/td\u003e\n\u003ctd\u003e1.2 x 7.1 x 10.0 cm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temp\u003c\/td\u003e\n\u003ctd\u003e0 to 55 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Consumption\u003c\/td\u003e\n\u003ctd\u003e1.45 W max (NX bus power) \/ External supply: 24 VDC (0.05 A max)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNumber of Analog Outputs\u003c\/td\u003e\n\u003ctd\u003e4 channels\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eLinear Output Range\u003c\/td\u003e\n\u003ctd\u003e-10 to +10 V\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eConversion Resolution\u003c\/td\u003e\n\u003ctd\u003e15 Bit\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eConversion Speed\u003c\/td\u003e\n\u003ctd\u003e0.04 ms\/unit\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSignal Processing Mode\u003c\/td\u003e\n\u003ctd\u003eSynchronous I\/O refreshing\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTerminal Type\u003c\/td\u003e\n\u003ctd\u003ePush-in terminal block\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eEnclosure Rating\u003c\/td\u003e\n\u003ctd\u003eIP20\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eDeterministic Network Bus \u0026amp; Hardware Integration\u003c\/h3\u003e\n\u003cp\u003eIntegrated into Sysmac NX backplane structures, the unit processes digital command structures across Profinet \/ EtherNet\/IP deterministic networks with microsecond-level synchronization. High backplane bus communication velocity allows all 4 output channels to update simultaneously without network jitter. The module maintains full firmware flash compatibility across NX series coupler units, enabling seamless dynamic I\/O density scaling within compact industrial enclosures.\u003c\/p\u003e\n\u003ch3\u003eStandard Commercial Deliverables\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e1 x Omron NX-DA3605 Analog Output Unit\u003c\/li\u003e\n\u003cli\u003e1 x Push-in Terminal Block (Front Assembly)\u003c\/li\u003e\n\u003cli\u003e1 x Hardware Instruction Sheet\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eCabinet Installation \u0026amp; Field Cabling Directives\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eDIN Rail Engagement\u003c\/strong\u003e: Hook the top slot onto a standard 35 mm DIN rail and press the module backward until the lower locking tab latches securely.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003ePush-in Wire Termination\u003c\/strong\u003e: Strip solid conductors or insulated ferrules to the specified length and push directly into terminal slots without tools.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eBackplane Bus Insertion\u003c\/strong\u003e: Align side guide connectors with the preceding NX module and slide laterally until the backplane contacts click together.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eAnalog Signal Shielding\u003c\/strong\u003e: Use shielded twisted-pair cables for -10 to +10 V voltage loops and terminate shields to the functional ground rail.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003ePower Separation\u003c\/strong\u003e: Route analog signal lines in isolated wire ducts separated from high-voltage AC mains and drive output cables.\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eFrequently Asked Questions\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cp\u003eIs hot-swapping permitted for the NX-DA3605 during active CPU operation?\u003c\/p\u003e\n\u003cp\u003eNo. Backplane power and external supply power must be completely isolated before inserting or removing the slice module from the rack.\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003eHow does synchronous signal processing execute output updates?\u003c\/p\u003e\n\u003cp\u003eSynchronous processing updates all 4 voltage outputs concurrently in strict synchronization with the CPU primary execution cycle.\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003eWhat wire gauge range is compatible with the push-in terminal connectors?\u003c\/p\u003e\n\u003cp\u003eThe push-in terminal block accepts solid or stranded wire with ferrules ranging from AWG 24 to AWG 16 (0.25 to 1.5 mm2).\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003eWhat is the conversion speed of the internal DAC circuitry?\u003c\/p\u003e\n\u003cp\u003eThe internal digital-to-analog converter operates at a high conversion rate of 0.04 ms per unit across all active output channels.\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003eHow is analog signal integrity maintained against industrial EMI?\u003c\/p\u003e\n\u003cp\u003eDifferential circuit topology paired with shielded twisted-pair cabling prevents external electromagnetic interference on voltage loops.\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003eDoes the NX-DA3605 support individual channel power disabling?\u003c\/p\u003e\n\u003cp\u003eUnused channels can be disabled within Sysmac Studio hardware settings to optimize internal processing and reduce power dissipation.\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003eHow is cross-platform firmware flash compatibility handled?\u003c\/p\u003e\n\u003cp\u003eSysmac Studio automatically checks and matches module revision codes against system controller firmware rules during project download.\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003eWhat happens to the analog output signal if backplane communication fails?\u003c\/p\u003e\n\u003cp\u003eOutput behavior upon bus fault (such as hold last value or clear to 0 V) is configurable through the master controller settings.\u003c\/p\u003e\n\u003c\/li\u003e\n\u003c\/ul\u003e","brand":"Omron","offers":[{"title":"Default Title","offer_id":47306669392045,"sku":"NX-DA3605","price":100.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0733\/1613\/9181\/files\/NX-DA3605_3.jpg?v=1790221663","url":"https:\/\/www.maxwellplc.com\/products\/nx-da3605-omron-analog-output-module-sysmac-nx-series","provider":"Maxwell PLC Ltd","version":"1.0","type":"link"}