{"product_id":"imdso03-abb-infi-90-digital-output-module","title":"IMDSO03 ABB Infi 90 Digital Output Module","description":"\u003cp\u003eThe\u003cspan\u003e \u003c\/span\u003e\u003cstrong\u003eABB IMDSO03\u003c\/strong\u003e, also cataloged as the\u003cspan\u003e \u003c\/span\u003e\u003cstrong\u003eIMDSO03\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003eDigital Output Module, operates as a dedicated hardware component for discrete output switching and load actuation within Network 90 and Bailey Infi 90 control systems. The module transfers electrical output states through isolated digital channels supporting DC load control up to 160 VDC with controlled leakage and surge current characteristics.\u003c\/p\u003e\n\u003ch3\u003eModule Identification\u003c\/h3\u003e\n\u003cp\u003eThe IMDSO03 is supplied as a fixed-model digital output slave module for ABB Bailey Infi 90 architectures. No configurable suffix matrix or field-selectable electrical variant is defined in the provided technical documentation.\u003c\/p\u003e\n\u003ch3\u003eElectrical Characteristics\u003c\/h3\u003e\n\u003ctable class=\"w-fit min-w-(--thread-content-width)\"\u003e\n\u003cthead\u003e\n\u003ctr class=\"firstRow\"\u003e\n\u003cth class=\"last:pe-10\"\u003eParameter\u003c\/th\u003e\n\u003cth class=\"last:pe-10\"\u003eSpecification\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eIMDSO03\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eABB\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003eDigital Output Module\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSeries\u003c\/td\u003e\n\u003ctd\u003eBailey Infi 90\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eManufacturer\u003c\/td\u003e\n\u003ctd\u003eABB\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOrigin\u003c\/td\u003e\n\u003ctd\u003eSweden\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e0.7 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eShipping Dimensions\u003c\/td\u003e\n\u003ctd\u003e17.8 x 5.1 x 33.0 cm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temp\u003c\/td\u003e\n\u003ctd\u003e0 deg C to 70 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Requirements\u003c\/td\u003e\n\u003ctd\u003e+5.00 VDC +\/-0.25 VDC at 150 mA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Consumption\u003c\/td\u003e\n\u003ctd\u003e0.75 W nominal\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMax. Load Voltage\u003c\/td\u003e\n\u003ctd\u003e5 VDC to 160 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMax. Load Current\u003c\/td\u003e\n\u003ctd\u003e1.0 A at 25 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eLoad Current at 50 deg C\u003c\/td\u003e\n\u003ctd\u003e0.9 A\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eLoad Current at 70 deg C\u003c\/td\u003e\n\u003ctd\u003e0.5 A\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMax. Off Leakage Current\u003c\/td\u003e\n\u003ctd\u003e2.0 mA at 70 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMax. On Voltage Drop\u003c\/td\u003e\n\u003ctd\u003e2.1 V at 1.0 A, 25 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMax. Surge Current\u003c\/td\u003e\n\u003ctd\u003e2 A for 1 second\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eIsolation\u003c\/td\u003e\n\u003ctd\u003e300 VRMS between output\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTariff Code\u003c\/td\u003e\n\u003ctd\u003e8537101190\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePlace of Shipment\u003c\/td\u003e\n\u003ctd\u003eXiamen, China\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003ch3\u003eBackplane Bus and Output Isolation\u003c\/h3\u003e\n\u003cp\u003eThe IMDSO03 exchanges output command states through the Infi 90 backplane communication structure. Output channels are electrically isolated to 300 VRMS between outputs to reduce fault propagation between external field circuits.\u003c\/p\u003e\n\u003cp\u003eI\/O density scaling inside multi-module cabinet installations should consider aggregate thermal loading when adjacent output modules operate continuously near maximum current limits. Forced cabinet airflow may be required in high-density rack assemblies operating at elevated ambient temperature conditions.\u003c\/p\u003e\n\u003cp\u003eFirmware flash compatibility should be verified against the installed process control firmware revision before rack commissioning or module replacement procedures.\u003c\/p\u003e\n\u003ch3\u003eEngineering FAQ\u003c\/h3\u003e\n\u003cp\u003e\u003cstrong\u003eQ: Does the IMDSO03 support inductive load switching directly?\u003c\/strong\u003e\u003cbr\u003eA: Inductive loads may require external suppression devices such as flyback diodes or RC snubbers to reduce transient voltage stress during output de-energization.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ: Can the module outputs be paralleled for increased current capacity?\u003c\/strong\u003e\u003cbr\u003eA: Parallel output operation is not specified in the provided documentation and should not be implemented without manufacturer validation.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ: What occurs if the ambient temperature increases above 50 deg C?\u003c\/strong\u003e\u003cbr\u003eA: Maximum supported load current decreases with increasing ambient temperature. The specified load current is reduced to 0.5 A at 70 deg C.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ: Is hot insertion supported during rack operation?\u003c\/strong\u003e\u003cbr\u003eA: Hot-swap operation is not defined in the supplied specifications. Standard industrial maintenance practice is to isolate rack power before module replacement.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ: What wiring practice is recommended for minimizing output noise coupling?\u003c\/strong\u003e\u003cbr\u003eA: Digital output wiring should be physically separated from analog instrumentation conductors and terminated using grounded shield practices where applicable.\u003c\/p\u003e\n\u003chr\u003e\n\u003ch3\u003eInstallation and Wiring Notes\u003c\/h3\u003e\n\u003cul class=\"list-paddingleft-2\"\u003e\n\u003cli\u003e\n\u003cp\u003eVerify output load polarity before field termination.\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003eMaintain proper torque on terminal connections to prevent thermal loosening during operation.\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003eRoute high-current output conductors separately from low-level signal wiring.\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003eConfirm cabinet grounding continuity before energizing the module.\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003eInspect field wiring insulation for degradation when switching high-voltage DC loads.\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003eAvoid obstructing rack ventilation openings in high-density cabinet layouts.\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003eUse anti-static handling procedures during module installation and removal.\u003c\/p\u003e\n\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eOrdering Information\u003c\/h3\u003e\n\u003cul class=\"list-paddingleft-2\"\u003e\n\u003cli\u003e\n\u003cp\u003e1 x ABB IMDSO03 Digital Output Module\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003eAnti-static protective packaging\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003eIndustrial-grade external shipping carton\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003eOptional rack hardware and field termination accessories supplied separately\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003eDocumentation availability depends on shipment configuration\u003c\/p\u003e\n\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eLogistics Information\u003c\/h3\u003e\n\u003cp\u003eDelivery time: 3-5 days when payment finish. Shipment through DHL, FedEx, or UPS using anti-static industrial packaging with reinforced internal cushioning protection for electronic control assemblies.\u003c\/p\u003e","brand":"ABB","offers":[{"title":"Default Title","offer_id":46021145231533,"sku":"IMDSO03","price":88.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0733\/1613\/9181\/files\/IMDSO03-1.jpg?v=1779845881","url":"https:\/\/www.maxwellplc.com\/products\/imdso03-abb-infi-90-digital-output-module","provider":"Maxwell PLC Ltd","version":"1.0","type":"link"}